Figure 1.6 Overload Trip Curves - Rockwell Automation SMC Dialog Plus User Manual

Table of Contents

Advertisement

Class 10
1000.0
100.0
10.0
1.0
0.1
1
2
3
4
5
6
7
8
9
Multiples of FLC
Approximate trip time for 3-phase balanced
condition from cold start.

Figure 1.6 Overload Trip Curves

Class 15
10000.0
1000.0
100.0
10.0
1.0
10
1
2
3
4
Multiples of FLC
Figure 1.7 Restart Trip Curves after Auto Reset
Class 20
10000.0
1000.0
100.0
10.0
1.0
5
6
7
8
9
10
1
2
Multiples of FLC
Approximate trip time for 3-phase balanced
condition from cold start.
100000
1000
100
10
1
0
100%
Percent Full Load Current Setting
Product Overview
10000.0
1000.0
100.0
10.0
1.0
3
4
5
6
7
8
9
10
1
Multiples of FLC
1000%
1-7
Class 30
2
3
4
5
6
7
8
9
10
Class 10
Class 15
Class 20
Class 30
Auto Reset Times:
Class 10 = 90s
Class 15 = 135s
Class 20 = 180s
Class 30 = 270s