(3) Although oxygen concentration measurement "C" has fallen lower than the hysteresis set
value, that measurement exceeds the hysteresis set value before the preset delayed time
has elapsed. So, the alarm is not canceled.
(4) Oxygen concentration measurement "D" has fallen below the hysteresis set value and the
preset delayed time during measurement has elapsed, so the alarm is canceled.
8.3.3

Alarm Setting

Set the alarm setpoints following Table 8.7 listing parameter codes.
Table 8.7
Oxygen concentration high-high alarm setpoint
Oxygen concentration high alarm setpoint
Oxygen concentration low alarm setpoint
Oxygen concentration low-low alarm setpoint
Humidity high-high alarm setpoint
Humidity high alarm setpoint
Humidity low alarm setpoint
Humidity low-low alarm setpoint
Mixing ratio high-high alarm setpoint
Mixing ratio high alarm setpoint
Mixing ratio low alarm setpoint
Mixing ratio low-low alarm setpoint
Oxygen concentration alarm hysteresis
Humidity alarm hysteresis
Mixing ratio alarm hysteresis
Delayed alarm action
Oxygen concentration high-high alarm detection
Oxygen concentration high alarm detection
Oxygen concentration low alarm detection
Oxygen concentration low-low alarm detection
Humidity high-high alarm detection
Humidity high alarm detection
Humidity low alarm detection
Humidity low-low alarm detection
Mixing ratio high-high alarm detection
Mixing ratio high alarm detection
Mixing ratio low alarm detection
Mixing ratio low-low alarm detection
Parameter Codes for Alarms
Set item
<8. Detailed Data Setting>
Parameter code
Set value
D01
0-100% O
D02
0-100% O
D03
0-100% O
D04
0-100% O
D05
0-100% H
D06
0-100% H
D07
0-100% H
D08
0-100% H
D11
0-1 kg/kg
D12
0-1 kg/kg
D3
0-1 kg/kg
D14
0-1 kg/kg
D30
0-9.9% O
D31
0-9.9% H
D32
0-0.1 kg/kg
D33
0-255 seconds
D41
0 Not detected
1 Detected
D42
0 Not detected
1 Detected
D43
0 Not detected
1 Detected
D44
0 Not detected
1 Detected
D45
0 Not detected
1 Detected
D46
0 Not detected
1 Detected
D47
0 Not detected
1 Detected
D48
0 Not detected
1 Detected
D51
0 Not detected
1 Detected
D52
0 Not detected
1 Detected
D53
0 Not detected
1 Detected
D54
0 Not detected
1 Detected
IM 11M12A01-04E
8-9
2
2
2
2
O
2
O
2
O
2
O
2
2
O
2
11th Edition : Jul. 19, 2017-00