CAUTION
• Measurement range switching function by an external contact input is available for analog
output 1 only and the range is fixed to 0-25%O
• To conduct a semi-automatic calibration, be sure to set the Calibration setup mode to "Semi-
automatic" or "Automatic".
8.5.2

Setting Input Contact

To set the input contacts, follow the parameter codes given in Table 8.13.
Table 8.13
Set item
Input contact 1 (function)
Input contact 2 (function)
Input contact 1 (action)
Input contact 2 (action)
8.5.3

Default Values

When the analyzer is delivered, or if data are initialized, the input contacts are all open.
8.6

Other Settings

8.6.1

Setting the Date-and-Time

The following describe how to set the date-and-time. Automatic calibration works following this
setting.
Use parameter code "F10" to set the date-and-time.
Parameter Codes for Input Contact Settings
Parameter code
E01
E02
E03
E04
<8. Detailed Data Setting>
.
2
Set value
0 Invalid
1 Calibration gas pressure decrease
2 Measuring range change
3 Calibration
4 Unburnt gas detection
0 Invalid
1 Calibration gas pressure decrease
2 Measuring range change
3 Calibration
4 Unburnt gas detection
0 Operated when closed
1 Operated when open
0 Operated when closed
1 Operated when open
IM 11M12A01-04E
11th Edition : Jul. 19, 2017-00
8-13