Electrical connections
Installing the transmitters in non-explosion-hazard areas:
The explosion-protection markings has to be removed from the transmitter.
Once the transmitter has been used after installation in this manner, it may
never be installed in explosion-hazard areas.
The maximum possible cable lengths can be found in the table on page 21.
In this table, select the line, " Number of transmitters = 1".
Explosion-hazard area, zone 2 or non-explosion hazard
+24 V
4 to 20 mA
Installing fieldbus communication on the transmitter
— The transmitter can be connected to a certified intrinsically safe fieldbus
system, which supports FISCO (Fieldbus intrinsically safe concept).
— The PROFIBUS PA transmission technology for intrinsically safe applica-
tions is MBP. MBP stands for:
– Manchester Coding (M)
– Bus Powered (BP)
— 5 transmitters can be connected to a segment with a typical segment cur-
rent of 100 mA.
Install the 2-wire connection cable in the cable gland, cut it to length and
strip off the insulation (approx. 80 mm).
Shorten the shield (if installed) to prevent short-circuiting.
Connect cable:
1 Use a 4-pole terminal block (X7), Part No. 83 16 268, for the
Dräger Polytron 7000 – Observe the polarity of the connections. Cut excess
wires short or
2 secure them in center terminals (Part No. 83 16 422).
1 Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station
for future use during commissioning.
Refit raincover (protection against dust and splashing water).
Insert 4-pole (X7) terminal block into left holder.
14
CAUTION
without a safety barrier
CAUTION
Non-explosion-hazard area
1
+
4 ... 20 mA
+
0 V
Control unit
X7
X8
2