4-wire connection

— Connection to central device with at least 4-wire cable, 0.5 (AWG 20) to
2
2.5 mm
(AWG 13).
Installing the LON Communication on the transmitter
— For installation using LON communication up to 63 Polytron 7000 can be
connected to a four wire cable in any configuration including bus, star, loop
and mixed.
X8
Insert the 4-wire connecting cable in the cable gland, cut it to length and
strip the insulation (approx. 80 mm).
Shorten the shield (if installed) to prevent short-circuiting:
Connect cable
1 4-pin terminal for Dräger Polytron 7000 – observe polarity.
Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station
for future use during commissioning.
Refit raincover (protection against dust and splashing water).
Installing the transmitter in non-explosion-hazard areas:
With 4-core connection the transmitter has no Ex protection. Once the trans-
mitter has been used after installation in this manner, it may never be
installed in explosion-hazard areas. Explosion hazard!
X7
X8
CAUTION
Electrical connections
X7
X8
23