Electrical connections

— The electrical wiring may be laid and connected only by a qualified electri-
cian, who must also comply with the appropriate regulations – a screened
or unscreened cable (such as LiY, LiYCY) may be used.

2-wire connection

— Connection to central device with at least 2-wire cable, 0.5 (AWG 20) to
2
2.5 mm
(AWG 13).
Installing the 4 to 20 mA current loop on the transmitter
— For currents of 3 to 22 mA, a DC voltage between 16.5 V DC (3 mA),
or 8.0 V DC (22 mA) and 30 V DC must be present at the transmitter.
Fit 2-wire connecting cable in cable gland, cut to length and strip ends
(approx. 80 mm / 3.15").
Shorten the shield (if installed) to prevent short-circuiting:
Connect cable
1 Use a 4-pole terminal block (X8), Part No. 83 16 268, for the
Dräger Polytron 7000 – Observe the polarity of the connections.
Cut excess wires short or
2 secure them in centre terminals (Part No. 83 16 422).
1 Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station
for future use during commissioning.
Refit raincover (protection against dust and splashing water).
Connecting to the central unit
Connect shield to earth of central unit (e.g. housing, earth bar, etc.).
Connecting the Dräger Polytron 7000 transmitter to a Dräger control unit
(such as Regard, QuadGard, Unigard or Polytron):
— Further information about the connection can be found in the instructions
for the Dräger control unit.
Connecting the Dräger Polytron 7000 transmitter to control units with
a 4 to 20 mA interfaced made by other manufacturers:
— For operation together with control units made by other manufacturers, care
must be taken that the voltage at the transmitter does not drop below 16.5 V
at a current of 3 mA and 8.0 V at a current of 22 mA. The supply voltage,
the resistance of the cable and the load and the resistance of any installed
safety barrier must be taken into account.
— Further information about the connection can be found in the instructions
for the control unit being used.