Installing the transmitter

Installing the docking station

— If the transmitter is to be installed in a Zone 2 explosion-hazard area, select
a location with low exposure to mechanical risk.
— Docking station is installed vertically (transmitter with sensor facing down)
in an area with low vibrations and stable temperatures – near the possible
leak.
— A space of at least 15 cm (6") must be maintained above the transmitter for
installation of the measuring unit.
— A space of at least 10 cm (4") – preferably 30 cm (12") – must be maintained
below the docking station to permit access for maintenance.
Unpack the docking station.
1 Remove raincover (protection against dust and splashing water).
2 Remove the 4-pole terminal block (Part No. 83 16 268), keep it in a safe
place and insert it again after completion of the installation work.
A drilling template is provided on page 139. The mounting holes are
66 ±4mm (2.6 ± 0.16") apart.
Spacers (e.g. mounting bracket 68 09 951) must be used to prevent any
twisting of the housing when installed on uneven surfaces.
If the measuring unit is not to be mounted at this time:
Refit the raincover (protection against dust and splashing water).
For Multidrop installation only:
(see page 18)
Installing the Daisy Chain kit
Part No. 83 17 282
3 Break or drill out the prepared breakthrough for the second cable gland
from the inside of the docking station.
The hole should have a diameter of 20.5 mm.
Check that the docking station has no loose parts, and clean it if necessary.
Insert the nut of the cable gland into the docking station.
Screw in the cable gland from the outside of the docking station and tighten
it.
10
CAUTION
1
2
3