3-Wire Connection - Dräger Polytron 7000 Instructions For Use Manual

Approved as type p3u and p3fb. transmitter for electrochemical sensors
Hide thumbs Also See for Polytron 7000:
Table of Contents

Advertisement

Electrical connections

3-wire connection

— Connection to central device with at least 3-wire cable, 0.5 (AWG 20) to
2
2.5 mm
(AWG 13).
The supplied ferrite sleeves are to be used when installing the transmitter in
three-wire technology.
A ferrite sleeve must be pushed onto each core prior to connecting the cable
to the four-pole terminal in the docking station.
Installing the 4 to 20 mA current loop on the transmitter
Install the 3-wire connection cable in the cable gland, cut it to length and
strip off the insulation (about 80 mm).
Shorten the shield (if installed) to prevent short-circuiting:
Connect cable
1 4-pin terminal for Dräger Polytron 7000 – observe polarity.
Slide connecting terminal back into holder.
Secure cable in holder.
Fold up the installation notes and place them in the Dräger docking station
for future use during commissioning.
Refit raincover (protection against dust and splashing water).
Connection to the control unit
Connect shield to earth of central unit (e.g. housing, earth bar, etc.).
Connecting the Dräger Polytron 7000 transmitter to a Dräger control unit
(such as Regard, QuadGard, Unigard or Polytron):
— Further information about the connection can be found in the instructions
for the Dräger control unit.
— When operated from the mains supply, the Polytron control unit provides a
supply voltage of at least 20 V. This must be taken into account when de-
termining the maximum cable length (see the table on page 21).
— Unigard is not suitable for the connection of a Polytron 7000 transmitter
equipped with a relay or pump module.
Connecting the Dräger Polytron 7000 transmitter to control units with
a 4 to 20 mA interfaced made by other manufacturers:
— Further information about the connection can be found in the instructions
for the control unit being used.
Installing the transmitter in non-explosion-hazard areas:
Remove the explosion-protection markings from the transmitter. Once the
transmitter has been used after installation in this manner, it may never be
installed in explosion-hazard areas. Explosion hazard!
— When installing a transmitter in a non-explosion-hazard area, connect the
cable shield and the negative pole of the supply voltage to earth at the
switch cabinet or distribution panel.
16
CAUTION
CAUTION
X8
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents