3-00: Frequency Upper limit(Hz) : 0.01 - 650.00
3-01: Frequency Lower limit(Hz) : 0.01 - 650.00
※ Note: When 3-01 = 0 Hz and frequency command is 0 Hz , the inverter will stop at 0 speed.
When 3-01 > 0 Hz and frequency command ≦ 3-01 , the inverter will output 3-01 preset
value.
3-02 : Acceleration Time #1 ( ( ( ( second) ) ) ) : 0.1 – 3600.0
3-03 : Deceleration Time #1 ( ( ( ( second) ) ) ) : 0.1 – 3600.0
3-04 : S Curve of First Acceleration Stage( ( ( ( second) ) ) ) : 0.0 – 4.0
3-05 : S Curve of Second Acceleration Stage( ( ( ( second) ) ) ) : 0.0 – 4.0
3-06 : Acceleration Time #2 ( ( ( ( second) ) ) ) : 0.1 – 3600.0
3-07 : Deceleration Time #2 ( ( ( ( second) ) ) ) : 0.1 – 3600.0
3-08 : Jog Acceleration Time( ( ( ( second) ) ) ) : 0.1 –25.5
3-09 : Jog Deceleration Time( ( ( ( second) ) ) ) : 0.1 – 25.5
Formula for calculating acceleration and deceleration time: The denominator is base on the
1.)
rated frequency of motor.
Acceleration time = 3-02 (or 3-06) x
2.)When 5-00 – 5-06 is set 06 (the second acceleration and deceleration time) , the first
acceleration/ deceleration/ S curve or the second acceleration/ deceleration/ S curve will be set
by ON the external input terminal.
3.) When 5-00 – 5-06 is set 05 (Jog), Jog run is controlled by external terminals. The acceleration
and deceleration action will be at Jog acceleration and deceleration time.
4.)When 5-00 – 5-06 is set as 05(Jog) and 06(acceleration and deceleration time toggle), to
change the acceleration and deceleration time by ON the external terminals, and the list
setting:
Function
preset value
5-00~5-05=05 Jog command
5-00~5-05=04
Toggle Acc/Dec time.
5.)When S curve time (3-04/3-05) is set as 0, the S curve is useless. Namely, acceleration and deceleration
Parameter Group 3 - Operating Parameters
( note )
Preset frequency
0-05
Acc/ Dec time 1(3-02/3-03) Acc/ Dec time 2 (3-06/3-07) JOG Acc/Dec time (3-08/3-09)
1-06 determines the output
frequency
Off
Off
3-00 (upper frequency limit)
3-01 (lower frequency limit)
,Deceleration time = 3-03 (or 3-07) x
1-06 determines the output
frequency
Off
On
4-26
Chapter 4 Software Index
Preset frequency
0-05
Run at 6-01Jog frequency
On
Off