Danger:
1.) 2-05=0000 and the inverter is set external terminal controlled ( 1-00=0001 ) , if the run switch is
ON as power is supplied, the inverter will auto start. It is recommend that to cut off the power
switch and run switch in case of injury to persons or machine as power is resupplied.
2.) 2-05=0001and the inverter is set external terminal controlled ( 1-00=0001 ) , if the run switch is
ON as power is supplied, the inverter will not auto start and flash STP1. It is necessary to
OFF the run switch and then ON to normally start.
2-06 : Delay-ON Timer (seconds): 0 ~ 300.0 second
As power on and 2-05=0000, the inverter will perform auto restart in the setting time for delay.
2-07: Error reset mode setting
2-07=0000as the inverter is detected the accident, please cut off the Run switch to perform reset, or
restarting does not work.
2-08: Kinetic Energy Back-up Deceleration Time:0.00~25.00 second
2-08 = 0 KEB function disable
2-08 ≠ 0 KEB function enable
Ex: 220V system
※ NOTE:
1.When 2-08 ≠ 0 , the momentary power loss and Restart is disabled,the inverter will do KEB
Function.
2.When power off , CPU detect the DC Voltage. KEB function enable when DC Voltage below than
190V ( 220V system ) or 380V ( 440V system ) .
3.When KEB function enabled,the inverter decelerate to zero by 2-08,and the inverter stop.
4.IF the power on signal enabled during the KEB function ,the inverter accelerate to original
frequency.
0000: Enable Reset Only when Run Command is Off
0001: Enable Reset when Run Command is On or Off