Fuse types
Drive input fuses are provided to disconnect the drive from power in the event that a
component fails in the drive's power circuitry. The drive's electronic protection circuitry is
designed to clear drive output short circuits and ground faults without blowing the drive input
fuses. Below table shows the VAT200 input fuse ratings.
To protect the inverter most effectively, use fuses with current-limit function.
RK5, C/T TYPE FUSE FOR VAT200
220V class(1φ)
U201N-
00K4
00K7
01K5
02K2
220v class(3φ)
U203N-
00K4
00K7
01K5
02K2
04K0
05K5
07K5
440 class(3φ)
U203X-
00K7
01K5
02K2
04K0
05K5
07K5
11K0
15K0
18K5
22K0
30K5
37K0
45K0
55K0
*Fuse ratings are based upon 250V fuses for 230V inverter, and 600V for 460V inverters
For UL, apply UL Designated Class RK5 (delay type fuses), CC or T (non delay fuses)
HP
KW
KVA
100% CONT
Output AMPS (A)
0.5
0.4
1.2
1
0.75
1.7
2
1.5
2.9
3
2.2
4.0
HP
KW
KVA
100% CONT
Output AMPS (A)
0.5
0.4
1.2
1
0.75
1.7
2
1.5
2.9
3
2.2
4.0
5
3.7
6.7
7.5
5.5
9.9
10
7.5
13.3
HP
KW
KVA
100% CONT
Output AMPS (A)
1
0.75
1.7
2
1.5
2.9
3
2.2
4.0
5
3.7
6.7
7.5
5.5
9.9
10
7.5
13.3
15
11.0
20.6
20
15.0
27.4
25
18.5
34.0
30
22.0
41.0
40
30.0
54.0
50
37.0
68.0
60
45.0
82.0
75
55.0
110.0
3-4
Chapter 3 Ambient Environment and Installation
Max.kk5
FUSE Rating(A)
3.1
10
4.5
15
7.5
20
10.5
25
Max.kk5
FUSE Rating(A)
3.1
8
4.5
12
7.5
15
10.5
20
17.5
30
26
50
35
60
Max.kk5
FUSE Rating(A)
2.3
6
3.8
10
5.2
10
8.8
20
13
25
17.5
30
25
50
32
60
40
70
48
80
64
100
80
125
96
150
128
200
Max.CC or T
FUSE Rating(A)
20
30
40
50
Max.CC or T
FUSE Rating(A)
10
15
20
30
50
60
70
Max.CC or T
FUSE Rating(A)
10
15
20
30
35
50
60
70
80
100
125
150
200
250