GE VAT200 Quick Start Manual page 48

Table of Contents

Advertisement

1-01 = 0002, Control mode is as below:
(1). Input signal is NPN:
※ Note: As 3 wire control mode is selected, the terminal S3 is not controlled by 5-02.
※ Note: 1-02=0001, the reverse command is unavailable.
1-02 : Prohibition of Reverse Operation 0000: Enable Reverse Command
1-02=0001, the reverse command is invalid.
1-03 : Keypad Stop Button 0000: Stop Button Enable
1-03=0000 , The STOP key is available for controlling the inverter to stop.
1-04 : Starting Method Selection
1.) 1-04=0000 : As starting, the inverter accelerates from 0 to target frequency in the set time.
2.) 1-04=0001 : As starting, the inverter accelerates to target frequency from the detected speed of
motor.
1-05 : Stopping Method
1.) 1-05=0000: the inverter will decelerate to 0Hz in preset deceleration time after receiving the stop
command.
S1 ( run )
S2 ( stop )
S3 (FWD/REV)
( 0V common )
COM
0001: Stop Button Disable
0000: Normal Start
0001: Enable Speed Search
0000: Controlled Deceleration-to- Stop with DC Injection Braking
(Rapid Stop)
0001: Free run stop
(2). Input signal is PNP:
0001: Disable Reverse Command
4-22
Chapter 4 Software Index
S1 ( run )
S2 ( stop )
S3 (FWD/REV)
24V (common)