run for 1 minute.
2. The heat sinking function will declining when the motor run at low speed. So the thermal relay
action level will decline at the same time.(The curve 1 will change to curve 2).
3. 9-09 = 0000 : set 0-05 as the rated frequency of the serve motor.
9-11 = 0000 : the inverter coast to stop as the thermal relay acts and flash OL1. Press the 'reset' or
the external reset terminal to continue to run
= 0001 : the inverter continues to run as the thermal relay acts and flash OL1. Till the
current decline to 103% or 113%(determined by 9-10), OL1 will disappear.
9-12: : : : Over Torque Detection Selection:
= 0000: : : : Disable Over Torque Operation
= 0001: : : : Enable Over Torque Operation Only if at Set Frequency
= 0002: : : : Enable Over Torque Operation while the Drive is in Run Mode
9-13: : : : Operation After Over Torque Detection is Activated:
= 0000: : : : Drive will Continue to Operate After Over Torque is Activated
= 0001: : : : Coast-to-Stop After Over Torque is Activated
9-14: : : : Over Torque Threshold Level (%): : : : 30-200%
9-15: : : : Over Torque Activation Delay Time (s): : : : 0.0-25.0
The over torque is defined as: the output torque is inside parameter 9-15, the voltage level(the inverter
rated torque is 100%) is over 9-14 parameter.
9-13 = 0000 : If there is over torque, the inverter can continue to run and flashes OL3 till the output
4-45