5.4 Routine inspection and period inspection

To ensure stable and safe operations, check and maintain the inverter regularly and
periodically.
The table below lists the items to be check to ensure stable and safe operations.
Check these items 5 minutes after the "Charge" indicator goes out to prevent service
persons from being hurt by residual electric power.
Items
Details
Confirm
temperature and
Circumstances
humidity around
around
the
the machine
machine
Are
inflammables
piled up around?
Any unusual vibration
from the machine
Installation
and grounding
Is the grounding
of the inverter
resistance correct?
Input power
Is the voltage of the
voltage
main circuit correct?
External
Are secure parts
terminals and
loose?
internal
Is the terminal base
mounting
damaged?
screws of the
Obvious rust stains
inverter
Deformed or crooked
Internal wiring
Any damage of the
of the inverter
wrapping of the
conducting wire
Heap of dust or
Heat sink
mingled trifles
Heap of conductive
metal or oil sludge
Printed
Discolored,
circuit board
overheated, or
burned parts
Unusual vibration and
noise
Cooling fan
Heap of dust or
mingled trifles
Heap of dust or
mingled trifles
Power
Check resistance
component
between
terminals
Any unusual odor or
leakage
Capacitor
Any
inflation
protrusion
Checking
period
Daily 1Year
the
there
each
or
5-13
Chapter 5 Troubleshooting and maintenance
Methods
Measure
with
Temperature:
thermometer
and
-10 – 40
hygrometer
Humidity: Below
according
to
95% RH
installation notices.
Visual check
No foreign matters
Visual, hearing
No foreign matters Secure screws
200V series: below
Measure
the
100Ω
resistance with a
400V series: below
multi-tester
10Ω
Voltage
Measure the voltage
conform with the
with a multi-tester
specifications
Visual check
Check with a
No abnormalities
screwdriver
Visual check
No abnormalities
Visual check
No abnormalities
Visual check
No abnormalities
Visual or hearing
check
No abnormalities
Visual check
Visual check
No abnormalities
No short circuit or
Measure with a
broken circuit in
multi-tester
three-phase output
Visual check
No abnormalities
Criteria
Remedies
o
C
Improve the
circumstances
Improve the
grounding
must
Improve input
voltage
Secure or send
back for repair
Replace or
send back for
repair
Clean up
heaped dust
Clean up or
replace the
circuit board
Replace the
cooling fan
Clean up
Clean up
Replace
power
component or
inverter
Replace
capacitor or
inverter