5. Commissioning
0
2
4
6
8
E
1
TEMP.: 68°
2
1
D
2
#
F
% $
AUTO
J
I
5"
Installer level - Menu (#PRIMARY LIMITS)
Parameter
Adjustment range
20 to 79 °C
MAX MIT
20 to 79 °C
(1)
MAX HP
¼ See chapter: "Setting the speed of the heating pump on the inside module", page 86
PERCENT PUMP MIT
(1)
¼ See chapter: "Setting the heating pump speed on the heat pump", page 86
MHR.PUMP SPEED
(1)
(1)
-20 to +5 °C
STOP HP:
25 to 40 °C
(1)
DEFROST MIN.T.
-10 to +20 °C
BIVALENCE.TEMP
(1)
(1) The parameter is only displayed if INSTALLATION} is set to EXTENDED
Installer level - Menu #SECONDARY LIMITS
Parameter
Adjustment range Description
20 to 95 °C
MAX.CIRC.A
20 to 95 °C
MAX.CIRC.B
20 to 95 °C
MAX.CIRC.C
OUT.ANTIFREEZE OFF, -8 to +10 °C
(1) (2)
OFF, 20 to 90 °C
HCZP D A
OFF, 20 to 90 °C
(1) (2)
HCZP N A
OFF, 20 to 90 °C
(1) (2)
HCZP D B
OFF, 20 to 90 °C
(1) (2)
HCZP N B
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f.
91
10
12
14
16
18
20
22
24
SUNDAY 11:45
!

:
<
STD
C002235-F-04
Description
Maximum temperature of the MIT
Maximum heat pump temperature
Heat pump shutdown temperature
Minimum defrosting temperature
Temperature at the bivalence point
Maximum temperature (Circuit A)
¼ "MAX.CIRC...", page 96
Maximum temperature (Circuit B)
¼ "MAX.CIRC...", page 96
Maximum temperature (Circuit C)
¼ "MAX.CIRC...", page 96
Outside temperature at which the installation's antifreeze protection
is activated.
Below this temperature the pumps are permanently on and the
minimum temperatures for each circuit are respected.
When NIGHT :STOP is set, the reduced temperature is maintained
in each circuit (Menu #SECONDARY INSTAL.P).
OFF: Antifreeze protection is not activated
Curve base temperature in Daytime mode (Circuit A)
Curve base temperature in Nighttime mode (Circuit A)
Curve base temperature in Daytime mode (Circuit B)
Curve base temperature in Nighttime mode (Circuit B)
5.6.3.

Professional settings

1. Access the installer level: Press key - for around 5 seconds.
2. Set the following parameters:

Turn the rotary button to scroll through the menus or

4
modify a value.
Press the rotary button to access the selected menu
4
or confirm a value modification.
¼ For a detailed explanation of menu browsing, refer
to the chapter: "Browsing in the menus", page 75.
AWHP MIT-IN iSystem
Factory setting
Customer setting
60 °C
60 °C
-15 °C
30 °C
10 °C
Factory setting
75 °C
50 °C
50 °C
+3 °C
OFF
OFF
OFF
OFF
24/09/2012 - 300027606-001-01