DeDietrich AWHP 6 MR Installation And Service Manual page 49

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
C3
C2
Configuration
24/09/2012 - 300027606-001-01
n Fitting the jumpers and bridges
C1
L1
L2
L3
N
C
S2
S3
Alim appoint électrique
Alim appoint électrique
BUS<>HP
BUS<>HP
*
1
n Output control
¼ For setting the BACKUP TYPE parameter, see: "Professional
settings", page 91
Single phase power supply: 230 V AC
Z
CAUTION
The earth conductor must be longer than the live and
neutral conductors.
C3
C2
C1
L1
L2
L3
N
Configuration
Alim appoint électrique
Alim appoint électrique
*
2
Three-phase
A
Single phase
Z
For the various options for setting the bridge, see the
*
paragraph below, "Setting the output".
CAUTION
Check that the clips are correctly connected to the tab as
poor contact may lead to the connection overheating.
Type
BACKUP TYPE
setting
Single phase /E2
/E1
C
S2
S3
BUS<>HP
BUS<>HP
Back-up
Output Bridge
Stage1
2 kW
Stage2
4 kW
Stage1 + 2 6 kW
Stage1
2 kW
4. Installation
M002393-E
between C2 and
C1
48