Recommended Cable Cross Section - DeDietrich AWHP 6 MR Installation And Service Manual

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
Appliance
Outside
Absorbed
module
electrical
power
Nominal
amperage
Maximal
amperage
(1)
Type
Power supply
Indoor
Power supply
module
(4)
Cable BUS
(1) 1 ~ : Single phase, 3 ~ : Three-phase
(2) Cable cross section (mm²)
(3) Circuit breaker
(4) Connection cable between outdoor and indoor module
(1)
Type
S-C
Curve C DJ
Single phase 3 x 6
32 A
Three-phase 5 x 4
25 A
(1) Cable cross section (mm²)
(2) Circuit breaker
24/09/2012 - 300027606-001-01
4.11.2.
The electrical characteristics of the mains power supply available
must correspond to the values given on the rating plate.
The cable will be carefully chosen according to the following
information:
4 Maximum intensity of the outdoor module. See table below.
4 Distance of the appliance from the original power supply.
4 Upstream protection.
4 Neutral operating conditions.
AWHP
6 MR
8 MR
MIT-IN
kW
1.50
2.10
A
6.8
9.34
A
13
19
1 ~
1 ~
(2)
3 x 2.5 3 x 4
S-C
Curve D
16 A
25 A
(3)
DJ
(2)
3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5
S-C
Curve C
10 A
10 A
(3)
DJ
3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5 3 x 1.5
(2)
S-C
n Connecting the electrical back-up
(2)

Recommended cable cross section

11 MR 11 TR
14 MR 14 TR
2.59
2.59
3.45
11.2
3.98
14.8
28
13
28
1 ~
3 ~
1 ~
3 x 6
5 x 2.5 3 x 6
32 A
16 A
32 A
10 A
10 A
10 A
16 MR 16 TR
3.45
4.03
4.03
5.37
17.7
5.99
13
29
13
3 ~
1 ~
3 ~
5 x 2.5 3 x 10
5 x 2.5 5 x 4
16 A
40 A
16 A
10 A
10 A
10 A
4. Installation
22 TR
27 TR
5.6
6.9
13.9
17.2
19
21
3 ~
3 ~
5 x 6
25 A
32 A
10 A
10 A
42