Advertisement

5. Commissioning
Installer level - Menu #SECONDARY INSTAL.P
Parameter
Adjustment range
NIGHT
DEC.
STOP
OFF / TEMPERATURE /
(1)
IN 0-10V
POWER %
0 to 10 V
(1) (5)
VMIN/OFF 0-10V
0 to 10 V
(1) (5)
VMAX 0-10V
(1)
0 to 100
CONS.MIN 0-10V
(5)
5 to 100
(1)
CONS.MAX 0-10V
(5)
0 to 15 minutes
H. PUMP DELAY
(6)
ON
ADAPT
OFF
LEG PROTEC
OFF
DAILY
WEEKLY
0 to 20 °C
OFFSET EVU
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED.
(2) The parameter can be set to the heating curve by pressing key f.
(3) The parameter is only displayed if the circuit is configured to 3WV or FAN CONVECTOR and the COOLING parameter is other than OFF.
(4) The parameter is only displayed if SCREED DRYING is other than OFF.
(5) The parameter is only displayed if the IN 0-10V parameter is not set to NO.
(6) The parameter is only displayed if a room sensor is connected.
95
Description
The lower temperature is maintained
(Night mode)
¼ "NIGHT", page 97
The boiler is stopped (Night mode)
¼ "NIGHT", page 97
Activating the control at 0-10 V
¼ "Function 0-10 V", page
98
Voltage corresponding to the
instruction set minimum
Voltage corresponding to the
instruction set maximum
Minimum set point temperature or
output
Maximum set point temperature or
output
Timing of the shutdown of the heating
pumps.
The timed heating pump shutdown
prevents the heat pump overheating.
Automatic adaptation of the heating
curves for each circuit with a room
sensor with an influence of >0.
The heating curves can only be
modified manually.
The anti legionella function acts to
prevent the development of legionella
in the dhw tank, these bacteria are
responsible for legionellosis.
Anti-legionella function not activated
The tank is overheated every day from
4:00 o'clock to 5:00 o'clock
The tank is overheated every Saturday
from 4:00 o'clock to 5:00 o'clock
Overheating flow temperature
AWHP MIT-IN iSystem
Factory setting Customer
setting
DEC.
OFF
0.5 V
10 V
5
100
4 minutes
ON
OFF
7 °C
24/09/2012 - 300027606-001-01