Installer Level - Menu #Primary Instal.p; Parameter; Adjustment Range Description; Factory Setting Customer Setting - DeDietrich AWHP 6 MR Installation And Service Manual

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
Installer level - Menu #SECONDARY LIMITS

Parameter

Adjustment range Description

(1) (2)
OFF, 20 to 90 °C
HCZP D C
OFF, 20 to 90 °C
(1) (2)
HCZP N C
50 to 79 °C
PRIM.TEMP.DHW
(1)
(1) The parameter is only displayed if INSTALLATION is set to EXTENDED
(2) The parameter can be set to the heating curve by pressing key f.

Installer level - Menu #PRIMARY INSTAL.P

Parameter
HP BUS
COOLING
(2)
SUM/WIN BAND
(2)
REVERS.TIMING
SUM/WIN
HP PUMP DELAY
DIFF.HP
MINI STOP HP
E. BL
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if the COOLING parameter is not set to OFF.
(3) Active when the BL contact is opened.
(4) Active when the BL contact is closed.
24/09/2012 - 300027606-001-01
Curve base temperature in Daytime mode (Circuit C)
Curve base temperature in Nighttime mode (Circuit C)
Boiler temperature setting if producing domestic hot water
(1)
Adjustment range
Description
Type of communication with the heat
ROE
pump
OO/ROE+
ROI+
TOR
OFF / ON / ON+DHW
Cooling
2 to 10 °C
Neutral band in which the inside module
is on standby
10 to 48 hours
Hot/Cold time delay reversal
15 to 30 °C
Used to set the outside temperature
above which heating will be shut down.
4
4
4
Heating is never shut down
NO
automatically
0 to 30 min
Post-operating time of the heating
pump on the heat pump
1 to 10 °C
Set point differential on the heat pump
3 to 30 min
Anti-short cycle time
(3)
Total shutdown of the installation. Frost
COMPLETE
protection not guaranteed.
Shutdown - Frost protection of the
(3)
PARTIAL
installation
(4)
User reset
USER RESET
Power cut off of the back-ups on the
(4)
BACK-UP MIT
inside module
Power cut off of the back-ups on the
(4)
AUCUN-APP+PAC
inside module + Power cut off of the
DHW tank back-ups + HP power cut off.
The installation is stopped. Frost
protection not guaranteed.
HP power cut off
(4)
COMPRESSOR
Power cut off of the back-ups on the
(4)
BACK-UP MIT DHW
inside module + Power cut off of the
DHW tank back-ups
Power cut off of the DHW tank back-ups
(4)
WWE ZUSATZHEIZ
Power cut off of the DHW tank back-
WWE.KOMP ZUSATZ.
ups + HP power cut off
(4)
The heating pumps are shut down.
The heat pump only starts up for
domestic hot water needs.
In this case the letter E and symbol
p are displayed.
5. Commissioning
Factory setting
OFF
OFF
65 °C
Factory setting Customer
setting
Keep the
TOR
factory setting.
OFF
4°C
24 hours
22 °C
1 mn
5°C
3 mn
1: PARTIAL
92