Combination With A Dhw Tank; Refrigeration Connection; Installing The Pipes - DeDietrich AWHP 6 MR Installation And Service Manual

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
4.7

Combination with a DHW tank

AWHP 6MR AWHP 8MR AWHP 11MR-TR AWHP 14MR-TR AWHP 16MR-TR AWHP 22TR AWHP 27TR
BL150
X
BL200
X
BL300
4.8

Refrigeration connection

24/09/2012 - 300027606-001-01
2
¼ For the connection of the outside temperature sensor, refer to
the chapter "Electrical Connections".
8800N003-C
In order to optimise domestic hot water production, the recommended
combinations of heat pumps and DHW tanks are:.
X
X
X
X
X
4.8.1.
4 Install the frigorific connection pipes between the inside and
4 Respect the minimum curve radii of 100 to 150 mm.
4 Respect the minimum and maximum lengths. ¼ See
Inserts
A
Ø4 wood screw
Z
X
X
WARNING
An incorrect DHW tank/heat pump combination may
adversely affect user comfort.
An incorrect combination may lead to overconsumption
subsequent to the repeated tripping of the back-ups.

Installing the pipes

DANGER
Only a qualified professional may carry out the installation
in conformity with in force legislation and standards.
outside modules.
chapter: "Location of the appliance", page 19.
If the frigorific connection between the outside module and the
inside module is less than 5 m, the following disruptions may
occur:
- Functional disruptions caused by a fluid overload
- Noise pollution caused by the circulation of the refrigerant
In this case, fit a refrigerant connection of at least 5 m by making
1 or 2 horizontal loops, as necessary, in order to limit such
annoyance and oil traps.
X
X
X
4. Installation
X
30