Filling The System - DeDietrich AWHP 6 MR Installation And Service Manual

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
Acidity (pH)
Conductivity at 25°C
Chlorides
Other components
Hardness of the water of the installation °f
24/09/2012 - 300027606-001-01
4
4
For an optimum functioning of the boiler, the water of the installation
must comply with following characteristics:
Output ≤ 70 kW
7.5 - 9
µS/cm 10 to 500
mg/l
< 50
mg/l
< 1
7- 15
°dH
4- 8.5
If a water treatment is necessary, De Dietrich
Thermique recommends the following manufacturers:
4
4
4
4
4
4.10.2.

Filling the system

CAUTION
Do not use glycol.
The heat pump components are not designed to be used
with glycol.
The use of glycol in the heating circuit invalidates the
warranty.
4 Fill the installation until a pressure of 1.5 to 2 bars is reached.
Water pressure display: See chapter: ¼ "Reading out
measured values", page 88.
4 Check for any water leaks.
4 Completely vent the indoor module and the installation for
optimum functioning.
Rinse the central heating installation with at least 3x
the volume of the central heating installation.
Flush the DHW pipes with at least 20 times the volume
of the pipes.
Cillit
Climalife
Fernox
Permo
Sentinel