Checking And Maintenance; General Instructions; Maintenance Operations To Be Performed; Cleaning The 400 Μm Filter - DeDietrich AWHP 6 MR Installation And Service Manual

Air / water heat pump
Hide thumbs Also See for AWHP 6 MR:
Table of Contents

Advertisement

AWHP MIT-IN iSystem
7

Checking and maintenance

7.1

General instructions

7.2

Maintenance operations to be performed

7.3
Cleaning the 400 µm filter
24/09/2012 - 300027606-001-01
CAUTION
4
4
4
Before carrying out any maintenance work requiring the
shutdown of the inside module, also cut the power supply
to the outside module to prevent any errors in
communication.
An annual inspection with sealing control is compulsory.
Schedule a service in cold periods to check the following points:
4 Thermal output by measuring the temperature difference between
the flow and the return.
4 Check the watertightness of the connections using a leak detector.
4 Check the watertightness of the water connections.
Preventive monitoring
4 Check the performance of the heat pump: Temperature control.
4 Check the water pressure in the installation.
4 Check that the filters are not obstructed.
4 Clean and dust the outdoor module.
To prevent clogging in the plate exchanger, a 400 µm filter is located
upstream of it. The filter is located in an isolating valve A.
A
Clean the filter during the annual service, after the first hour's running
on initial commissioning and if the flow rate drops (See table below).
outside unit

AWHP 6MR

AWHP 8MR

M002645-A
AWHP 11MR/
TR
Maintenance operations must be done by a qualified
engineer.
An annual inspection is compulsory.
Only original spare parts must be used.
Speed of the
Nominal
heat pump
water flow
heating pump
l/min
1
22
2
26
2
29
7. Checking and maintenance
Minimum flow rate
recommended
l/min
12
16
19
104