AWHP MIT-IN iSystem
Installer level - Menu #NETWORK
Parameter
(4)
FUNCT
(5)
PARALLEL CASC.
(3)
TIMER GENE P. CASC
(3)
INTER STAGE TIMER
(6)
SLAVE NUMBER
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if CASCADE: is set to NO
(3) The parameter is only displayed if CASCADE: is set to ON
(4) The parameter is only displayed if MASTER CONTROLLER is set to ON
(5) The parameter is only displayed if FUNCT is set to PARALLEL
(6) The parameter is only displayed if MASTER CONTROLLER is set to OFF
User level - Menu #SETTING
Parameter
Adjustment range Description
AUTO / 1 ... 10
(1)
PERMUT
(1) The parameter is only displayed if CASCADE: is on ON and MASTER CONTROLLER on ON
0
2
4
6
8
10
12
14
CASCADE
MASTER CONTROLER
E
1
SYSTEM NETWORK
2
FUNCT
1
D
2
INTER STAGE TIMER
F
#

!
% $
AUTO
J
I
STD
24/09/2012 - 300027606-001-01
(1)
Adjustment range Description
Operation in cascade: Successive
CLASSIC
tripping of the various generators in the
cascade according to needs
Functioning in parallel cascade: If the
PARALLEL
outside temperature is lower than the
PARALLEL CASC. value, all
generators are started up at the same
time
-10 to 20 °C
Outside temperature triggering all
stages in parallel mode
0 to 30 min
Minimum duration of post-operation of
the generator pump
1 to 30 min
Time delay for starting up or shutting
down generators.
2 to 10
Set the network address of the
secondary generator
This parameter is used to set the master boiler.
AUTO: The master boiler switches automatically
4
every 7 days
1 ... 10: The master boiler is always the one
4
defined by this value
16
18
20
22
24
ON
ON
TRADITIONAL
4'
9
<
C002409-C-04
n Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VM iSystem as slaves. Proceed as follows:
1. Set parameter CASCADE: to ON.
2. Select SYSTEM NETWORK and press the rotary button to go to
the specific menu.
5. Commissioning
Factory setting Customer setting
CLASSIC
10 °C
0 mn
4 mn
2