Electronic Expansion Valve Pi Control - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiAU18-715
2.3

Electronic Expansion Valve PI Control

Main Electronic Expansion Valve EV1 Control
Carries out the electronic expansion valve (Y1E) PI control to maintain the evaporator outlet
superheated degree (SH) at constant during heating operation to make maximum use of the
outdoor unit heat exchanger (evaporator).
SH = Ts1 - Te
The optimum initial value of the evaporator outlet superheated degree is 3°C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
Subcooling Electronic Expansion Valve EV3 Control
Makes PI control of the electronic expansion valve (Y3E) to keep the superheated degree
of the outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger.
SH = Tsh -Te
Function
SH : Evaporator outlet superheated degree (°C)
Ts1 : Suction pipe temperature detected by
thermistor R3T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
SH : Outlet superheated degree of evaporator (°C)
Tsh : Suction pipe temperature detected with the
thermistor R6T (°C)
Te : Low pressure equivalent saturation temperature
(°C)
Basic Control
(SH)
81

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents