Local Setting Mode Number

Example
To set the filter sign time to "filter contamination - heavy" for all units in a group:
Set mode No. to "10," setting switch No. to "0," and setting position No. to "02."
Table
Mode
Setting
No.
Switch
Note 1
No.
10
0
Filter contamination - heavy /
(20)
light (Setting of operating
hours for filter sign indication)
(Change setting when
reducing filter sign indication
time to half due to quick soiling
of filter)
1
Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
2
Remote control thermostat
(Set when remote control thermostat sensor
is used.)
3
Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
11
2
Indoor unit fan OFF when thermostat OFF in
(21)
cooling/heating
12
5
Automatic restart after power failure reset
(22)
*Note 4
13
0
High
(23)
Ceiling
1
Air flow direction selection (Change setting
when blocking kit is installed) *Note 3
4
Setting of air flow direction adjustment
range
Note:
1. Setting is made in all units in a group. To set for individual indoor units or to check the
2. The setting position No. is set to "01" at the factory, except for the following cases in which
3. Since drafts may result, carefully select the installation location.
4. When power returns, units resume the settings made before the power failure.
Caution
When "auto restart after power failure reset" is set, be sure to turn off air conditioners, then cut
off the power supply before conducting maintenance, inspection and other work. If the power
supply is cut off with the power switch left ON, air conditioners will automatically start operating
when the power supply is turned on.
5. Do not set any items other than those listed in the above table.
6. Functions that indoor units are not equipped with will not be displayed.
7. When returning to normal mode, "88" may be displayed on the LCD section of the remote
Test Operation
Setting Description
Long-Life
Type
Ceiling-suspended type (FHQ
only)
setting, use the mode Nos. (with "2" in upper digit) in parentheses ( ).
"02" is set.
Setting of air flow direction adjustment range 13(23)-4
Automatic restart after power outage. 12(22)-5
Remote control thermostat 10(20)-2
Filter sign indication (only for ceiling-mounted duct type) 10(20)-3
controller due to initialization operation.
Field Setting for SkyAir Indoor Unit
Setting Position No. *Note 2
01
Light
Approx.
Heavy
2,500
hours
Long-Life Filter
Use
Not use
ON
Fan OFF
OFF
2.7 m or Lower
2.7~3.5 m
F
Upward
Standard
02
03
Approx.
1,250
hours
OFF
ON
T
W
Downward
155