List of Malfunction Code
Malfunction
code
Outdoor
L1
Malfunction of PC board
Unit
L4
Malfunction of inverter radiating fin temperature rise
L5
Inverter compressor motor grounding, short circuit
L8
Inverter current abnormal
L9
Inverter start up error
LA
Malfunction of power unit
LC
Malfunction of transmission between inverter and
control PC board
P1
High voltage of capacitor in main inverter circuit
P4
Malfunction of inverter radiating fin temperature rise
sensor
PJ
Faulty combination inverter and fan driver,
Malfunction of capacity setting
System
U0
Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
U1
Reverse phase / open phase
U2
Power supply insufficient or instantaneous failure
U3
Check operation is not conducted.
U4
Malfunction of transmission between indoor and
outdoor units, etc.
U5
Malfunction of transmission between remote
controller and indoor unit
U5
Failure of remote controller PC board or setting
during control by remote controller
U7
Malfunction of transmission between outdoor units
U8
Malfunction of transmission between main and sub
remote controllers
U9
Malfunction of transmission between indoor unit and
outdoor unit in the same system
UA
Excessive number of indoor units etc.
UC
Address duplication of central remote controller
UE
Malfunction of transmission between central remote
controller and indoor unit
UF
System is not set yet
UH
Malfunction of system, refrigerant system address
undefined
UJ
Transmission error between outdoor unit and BP unit
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
320
Malfunction contents
9: Blink 8: ON 7: OFF
Page Referred
RA Indoor
SkyAir
BP Unit
Unit
Indoor Unit
345
346
347
SiAU18-715
Outdoor
Unit
376
377
378
379
380
381
382
383
384
385
387
389
353
390
392
394
396
397
398
400
401
355
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents