SiAU18-715
Check No. 02
Check for Thermistors
Disconnect the thermistor connector from PCB, then measure the resistance by using a tester.
Thermistor temperature and resistance characteristics
Temperature
Application
Troubleshooting
A
°C
-6.0
90.8
-4.0
81.7
-2.0
73.5
0.0
66.3
2.0
59.8
4.0
54.1
6.0
48.9
8.0
44.3
10.0
40.2
12.0
36.5
14.0
33.2
16.0
30.2
18.0
27.5
20.0
25.1
22.0
23.0
24.0
21.0
26.0
19.2
28.0
17.6
30.0
16.2
32.0
14.8
34.0
13.6
36.0
12.5
38.0
11.5
40.0
10.6
42.0
9.8
44.0
9.1
46.0
8.4
48.0
7.8
50.0
7.2
52.0
6.9
54.0
6.2
56.0
5.7
58.0
5.3
Heat exchanger
(Indoor/Outdoor units)
Suction air
Remote controller
Air
Outdoor air
Suction pipe
Troubleshooting for SkyAir Indoor Unit
Unit : kΩ
B
88.0
79.1
71.1
64.1
57.8
52.3
47.3
42.9
38.9
35.3
32.1
29.2
26.6
24.3
22.2
20.3
18.5
17.0
15.6
4.2
13.1
12.0
11.1
10.3
9.5
8.8
8.2
7.6
7.0
6.7
6.0
5.5
5.2
Radiator fin