SiAU18-715
7.34
Address Duplication of Central Remote Controller
UC
Remote
Controller
Display
Applicable
AII indoor unit models
Models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Address duplication of centralized remote controller
Defect of indoor unit PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Optional
controllers for
centralized control are
connected to the
indoor unit.
NO
YES
Troubleshooting for Outdoor Unit
Address duplication of
central remote controller
The setting must be
changed so that the
central remote control
address is not duplicated.
Replace indoor unit PC
board.
(Q0583)
397