2. Heating
2-1 Basic operation
In heating operation of the unit equipped with a humidifier, when "Interlocking of drain pump /
humidifier" (15(25)-3) is set to "yes" (02), the drain pump operates 20-min OFF and 3-min ON
repeatedly during compressor is in operation.
After compressor stops, residual operation will be conducted for 5 minutes.
2-1-1 When compressor stops during drain pump ON after compressor operation started
Drain pump
Compressor
2-1-2 When compressor stops during drain pump OFF after compressor operation started
Drain pump
Compressor
2-2
Operations when an occurrence of drain water level abnormality
2-2-a) Behavior between occurrence and recovery of drain water level abnormality
After compressor stops due to water level abnormality, drain pump is operated intermittenly, i.e. 5 min
ON, 5 sec OFF and 5 min ON. (*1) The intermittent operation is executed regardless of recovery of abn.
Water level during the intermittent operation. (*2) When the abn. water level can not be recovered, the
latter 5 min ON operation is continued until recovery of the abnormality. (*3) On above diagram, the
system operation in the event of a water level abnormality occurrence differs between the drain pump ON
and OFF. The details are as follows.
2-2-a)-1 When a water level abnormality occurs during drain pump ON
1 The same operation as 1-2-a) "Behavior between occurrence and recovery of drain water level
abnormality" in the mode of cooling or dry.
Water level abnormality
Drain pan
Normal
Drain pump
Compressor
Abnormal
Error processing
Normal
Note : ((2-2-a)-1 When a water level abnormality occurs during drain pump ON)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.
Function
20 min
ON
OFF
ON
OFF
20 min
ON
OFF
ON
OFF
Occurrence of drain water level abnormality
A 10
sec sec
ON
OFF
ON
OFF
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
3
20 min
min
3
min
Intermittent operation (*1)
5
5min
5min
sec
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Indoor Unit (SkyAir Models)
5min
5min
119