Indoor Unit (SkyAir Models)
Program Dry
The points of thermostat ON or OFF are determined according to the suction air temperature at
the startup of unit operation.
Operation
The set temperature and flow rate are not displayed on remote controller.
Function
1. Thermostat ON point (T
24°C≥ Ts>16°C
16°C≥ Ts
2. Operation condition
Setting of flow rate
Angle of flap
Air flow direction set with remote
controller
Auto-restart
If there is a power cut when the unit is operating, it will automatically resume the same operating
mode when the power is restored.
Function
Caution
When performing maintenance and the power supply is to be shut off, be sure to turn the remote
controller's ON/OFF switch OFF first.
Shutting the power supply switch off while the ON/OFF switch is still ON is dangerous because
the "power failure automatic reset function" will cause the indoor fan to start turning
immediately, or the outdoor unit fan to automatically start turning three minutes after the power
supply is turned back on.
122
Operation startup
Thermostat
ON
Thermostat
OFF
) according to suction air temp. (T
ON
Suction air temp
Ts>24°C
Compressor condition
(Differential)
T
(°C)
ON
Ts
Ts
16°C
ON
L operation
Set angle
Set angle
SiAU18-715
(S1120)
).
S
Td
(°C)
ON
1.5
1.0
1.0
OFF
OFF
Set angle
Set angle
Function