Electronic Expansion Valve Pi Control; Step Control Of Outdoor Unit Fans - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Si34-601A
2.3

Electronic Expansion Valve PI Control

Main Motorized Valve EV1 Control
Carries out the motorized valve (Y1E) PI control to maintain the evaporator outlet superheated
degree (SH) at constant during heating operation to make maximum use of the outdoor unit
heat exchanger (evaporator).
SH = Ts1 - Te
The optimum initial value of the evaporator outlet superheated degree is 5°C, but varies
depending on the discharge pipe superheated degree of inverter compressor.
Subcooling Motorized Valve EV2 Control
Makes PI control of the motorized valve (Y2E) to keep the superheated degree of the outlet gas
pipe on the evaporator side for the full use of the subcooling heat exchanger.
SH = Tsh -Te
2.4

Step Control of Outdoor Unit Fans

Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
STEP
No.
RXYQ5P
0
0
1
285
2
315
3
360
4
450
5
570
6
710
Cooling: 951
7
Heating: 941
Cooling: 951
8
Heating: 941
* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
Function
RXYQ8P
RXYQ10P
0
0
350
350
370
370
400
400
450
460
540
560
670
680
Cooling: 821
760
Heating: 800
Cooling: 796
Cooling: 821
Heating: 780
Heating: 800
SH : Evaporator outlet superheated degree (°C)
Ts1: Suction pipe temperature detected by
thermistor R6T (R7T) (°C)
Te : Low pressure equivalent saturation
temperature (°C)
SH : Outlet superheated degree of evaporator (°C)
Tsh : Suction pipe temperature detected with the
thermistor R5T (°C)
Te : Low pressure equivalent saturation
temperature (°C)
Fan revolutions (rpm)
RXYQ12P
(except Europe)
RXYQ12P
RXYQ14P
(Europe)
FAN1 FAN2 FAN1 FAN2 FAN1 FAN2
0
0
350
230
370
380
400
290
460
375
560
570
680
720
870
1091
870
1136
Basic Control
RXYQ16P
RXYQ18P
0
0
0
0
0
230
0
395
0
380
0
460
260
290
260
570
345
375
345
385
540
570
540
550
690
720
690
800
1061
1091
1061
1136
1106
1136
1106
1166
0
0
0
0
355
520
770
1106
1136
107