Malfunction Of Thermistor (R7T) For Outdoor Unit Liquid Pipe - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
7.13
Malfunction of Thermistor (R7T) for Outdoor Unit Liquid
Pipe
J7
Remote
Controller
Display
Applicable
AII outdoor unit models
Models
Method of
Malfunction is detected from the temperature detected by the liquid pipe thermistor.
Malfunction
Detection
Malfunction
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
372
Defect of thermistor (R7T) for outdoor unit liquid pipe
Defect of outdoor unit PCB (A1P)
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector is
connected to outdoor unit
PC board (A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R7T) from the outdoor
unit PC board.
(3.5kΩ~
360kΩ)
YES
Refer to thermistor resistance / temperature characteristics table on P405.
NO
NO
SiAU18-715
Connect the thermistor
and turn on again.
Replace the thermistor
(R7T).
Replace outdoor unit PC
board (A1P).
(Q0561)