3. OPERATION RANGE
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING
OUTDOOR
TEMPERA-
UNIT
DB 18 to 33 80% or
R35 · 45 · 60
WB 12 to 24
DB 18 to 33 80% or
RY35 · 45 · 60
WB 12 to 24
R71 · 100 · 125
DB 21 to 35
RP71 · 100 · 125
REP71 · 100 · 125
WB 14 to 25
RY71 · 100 · 125
DB 18 to 35
RYP71 · 100 · 125
RYEP71 · 100 · 125
WB 12 to 25
DB 21 to 35 80% or
RZP71 · 100 · 125
WB 14 to 25
DB 18 to 37 80% or
RQ71 · 100 · 125
WB 12 to 28
DB 18 to 37 80% or
RR71 · 100 · 125
WB 12 to 28
RZQ71 · 100 ·
DB 18 to 37 80% or
125 ·140
WB 12 to 28
RS50 · 60
DB 21 to 32
RKS35 · 50 · 60
RXS35 · 50 · 60
WB 14 to 23
3MKS50
DB 21 to 32
4MKS58 · 75 · 90
3MXS52 · 2MXS52
WB 14 to 23
4MXS68 · 80
DB 21 to 32
RMKS112 · 140 · 160
RMXS112 · 140 · 160
WB 14 to 23
290
INDOOR
OUTDOOR
TEMPERA-
HUMID
TURE
ITY
TURE
DB – 15 to 46
below
DB – 5 to 46
below
80% or
DB – 15 to 46
below
80% or
DB – 5 to 46
below
DB – 5 to 50
below
DB – 5 to 46
below
DB – 15 to 46
below
DB – 15 to 50
below
80% or
DB – 10 to 46
below
80% or
DB – 10 to 46
below
80% or
DB – 5 to 46
below
HEATING
INDOOR
OUTDOOR
TEMPERA-
UNIT
TURE
RY35 · 45 · 60
DB 15 to 27
RY71 · 100 · 125
RYP71 · 100 · 125
DB 15 to 27
RYEP71 · 100 · 125
RZP71 · 100 · 125 DB 15 to 27
RQ71 · 100 · 125 DB 10 to 27
RZQ71 · 100 ·
DB 10 to 27
125 · 140
RXS35 · 50 · 60
DB 10 to 30
3MXS52 · 2MXS52
DB 10 to 30
4MXS68 · 80
RMXS112 · 140 · 160 DB 10 to 30
DB: Dry bulb temperature (˚C)
WB: Wet bulb temperature (˚C)
The setting temperature range of the remote con-
troller is 16˚C to 32˚C.
4. INSTALLATION SITE
Regarding places for installation
• Is the air conditioner installed at a well-venti-
lated place where there are no obstacles
around?
• Do not use the air conditioner in the following
places.
a. Filled with much mineral oil such as cutting oil
b. Where there is much salt such as a beach area
c. Where sulfured gas exists such as a hot-spring
resort
d. Where there are considerable voltage fluctua-
tions such as a factory or plant
e. Vehicles and vessels
f. Where there is much spray of oil and vapor
such as a cookery, etc.
g. Where there are machines generating electro-
magnetic waves
h. Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer.
SiAU18-715
OUTDOOR
TEMPERATURE
DB
– 9 to 21
WB – 10 to 15.5
DB
– 9 to 21
WB – 10 to 15.5
DB
– 14 to 21
WB – 15 to 15.5
DB
– 9 to 21
WB – 10 to 15
DB – 19.5 to 21
WB – 20 to 15.5
DB
– 14 to 24
WB – 15 to 18
DB
– 14 to 21
WB – 15 to 15.5
DB
– 14 to 21
WB – 15 to 15.5