Transmission Error (Between Main And Sub Remote Controller) - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Troubleshooting for SkyAir Indoor Unit
5.13 Transmission Error
Controller)
U8
Remote
Controller
Display
Applicable
FFQ, FCQ, FBQ, FHQ
Models
Method of
In case of controlling with 2- remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Detection
Malfunction
Normal transmission does not continue for specified period.
Decision
Conditions
Supposed
Causes
Troubleshooting
346
(between Main and Sub Remote
Transmission error between Main remote controller and Sub remote controller
Connection among "Sub" remote controllers
Faulty remote controller PCB
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Controlling
NO
with 2-remote controller
YES
Both SS-1
NO
switches on remote
controllers are turned
to "Sub"
YES
SS-1switch
NO
on remote controller
PCB is turned to
"Main"
YES
SiAU18-715
Turn the SS-1switch of one
remote controller to "Main".
Turn OFF the power supply, and
restart operation
Turn OFF the power once and
restart operation.
Replace remote controller PCB if
any error is generated.
Turn the SS-1switch of one
remote controller to "Main".
Turn OFF the power supply, and
restart operation.
(Q0543)
Troubleshooting