Checking And Setting The Gas/Air Ratio - REMEHA Quinta Ace 30 Installation And User Manual

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Ace 30:
Table of Contents

Advertisement

7 Commissioning
Tab.32
Adjustment for BREEAM with gas type G20 (H gas)
Code
Display text
DP003
Abs. max fan
DHW
GP007
Fan RPM
Max CH
GP008
Fan RPM Min Minimum fan speed during
GP009
Fan RPM
Start
Tab.33
Adjustment for BREEAM with gas type G31 (propane)
Code
Display text
DP003
Abs. max fan
DHW
GP007
Fan RPM
Max CH
GP008
Fan RPM Min Minimum fan speed during
GP009
Fan RPM
Start
7.2.3

Checking and setting the gas/air ratio

Fig.45
Flue gas measuring point
38
Description
Maximum fan speed on Do­
mestic Hot Water
Maximum fan speed during
Central Heating mode
Central Heating + Domestic
Hot Water mode
Fan speed at appliance start
Description
Maximum fan speed on Do­
mestic Hot Water
Maximum fan speed during
Central Heating mode
Central Heating + Domestic
Hot Water mode
Fan speed at appliance start
AD-0000069-01
Warning
For the Quinta Ace 115, a flue gas pressure switch must be fitted
before setting the fan speeds for BREEAM. This switch has a
switch value of 600 Pa and protects against high flue pressures.
1. Adjust the fan speed according to the tables below. The setting can be
changed with a parameter setting.
Adjustment range
1400 - 7500 Rpm
1400 - 7500 Rpm
1000 - 4000 Rpm
1400 - 4000 Rpm
Adjustment range
1400 - 7500 Rpm
1400 - 7500 Rpm
1000 - 4000 Rpm
1400 - 4000 Rpm
2. Check the setting of the gas/air ratio.
Important
Make sure to apply the O
1. Unscrew the cap from the flue gas measuring point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
Warning
During measurement, seal the opening around the sensor fully.
Important
The flue gas analyser must have a minimum accuracy of
±0.25% O
.
2
The flue gas analyser must meet the requirements of BS 7927
or BS-EN 503793 and be calibrated according to the
manufacturer's requirements.
30
45
55
65
4100
5800
5600
6100
4100
5800
5600
6100
1550
1550
1650
1600
2500
2500
2500
2500
30
45
55
65
4100
5700
5600
6200
4100
5700
5600
6200
1550
1550
1650
1650
2500
3000
2500
2500
values specified for BREEAM.
2
7684359 - v.11 - 13122021
90
115
6600
7300
6600
7300
1600
1750
2500
2500
90
115
6500
7300
6500
7300
2100
1800
2500
3500