Technical data • Power Panel 400 with Automation Runtime
Mechanical characteristics
Outer dimensions
Width
Height
Depth
Front
Frame
Design
Membrane
Dark gray border around display
Light background
Gasket
Housing
Weight
Environmental characteristics
Ambient temperature
Operation
Storage
Transport
Relative humidity
Vibration
Operation (continuous)
Operation (occasional)
Storage
Transport
Shock
Operation
Storage
Transport
Protection type
7)
Altitude
1) Maintenance Controller Extended.
2) At max. specified ambient temperature: typ. 50 ppm (4 seconds) - worst-case 100 ppm (8 seconds).
3) Typical lifespan (at 50% buffer operation, temperature +25°C when off, +50°C when on).
Maximum lifespan in 24-hour operation (no buffer) 6 years at +25°C or 5 years at +50°C.
Maximum lifespan switched off: 2 years at +25°C or 1 year at +50°C.
4) The actual value depends on the operating system or diver being used.
5) At +25°C ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness
time.
6) Depending on the process or batch, there may be visible deviations in the color and surface structure.
7) Derating the maximum ambient temperature - typically 1°C per 1000 meters (from 500 meters above sea level).
226
See 4.11.2 "Temperature humidity diagram" on page 227
2 - 8 Hz: 7.5 mm amplitude / 8 - 200 Hz: 2 g / 200 - 500 Hz: 4 g
2 - 8 Hz: 7.5 mm amplitude / 8 - 200 Hz: 2 g / 200 - 500 Hz: 4 g
IP20 back side (only with installed CompactFlash card, inserted aPCI module
IP65 / NEMA 250 type 4X, dust and sprayed water protection (front side)
Table 85: Technical data - 4PP420.1043-B5 (Forts.)
4PP420.1043-B5
323 mm
260 mm
108 mm
Aluminum, naturally anodized
6)
Gray
Polyester
Similar to Pantone 432CV
Similar to Pantone 427CV
Flat gasket around display front
Metal
Approx. 4.2 kg (without aPCI interface modules)
0 to +50°C
-20 to +70°C
-20 to +70°C
2 - 9 Hz: 1.75 mm amplitude / 9 - 200 Hz: 0.5 g
2 - 9 Hz: 3.5 mm amplitude / 9 - 200 Hz: 1 g
15 g, 11 ms
30 g, 15 ms
30 g, 15 ms
or with an optional aPCI cover)
Max. 3000 m