Standards and certifications • Requirements for immunity to disturbances

4.3 High-speed transient electrical disturbances (burst)

Test carried out according to
EN 61000-4-4
AC power I/O
AC power inputs
AC power outputs
1)
DC power I/O >10 m
DC power inputs >10 m
DC power outputs >10 m
Functional ground connections,
signal lines and I/Os >3 m
Unshielded AC I/O >3 m
Analog I/O
Table 197: Test requirements - High-speed transient electrical disturbances (burst)
1) For EN 55024 without length limitation.
4.4 Surges
Test carried out according to
EN 61000-4-5
AC power I/O, L to L
AC power I/O, L to PE
DC power I/O, L+ to L-, >10 m
DC power I/O, L to PE, >10 m
DC power inputs, L+ to L-
DC power inputs, L to PE
DC power outputs, L+ to L-
DC power outputs, L to PE
Signal connections >30 m
All shielded cables
4.5 Conducted disturbances
Test carried out according to
EN 61000-4-6
AC power I/O
Table 199: Test requirements - Conducted disturbances
Power Panel 300/400 User's Manual V 2.10
Limits according to
EN 61000-6-2
±2 kV, criteria B
-
-
±2 kV, criteria B
-
-
±1 kV, criteria B
-
±1 kV, criteria B
Limits according to
EN 61000-6-2
±1 kV, criteria B
±2 kV, criteria B
±0.5 kV, criteria B
±0.5 kV, criteria B
-
-
-
-
±1 kV, criteria B
-
Table 198: Test requirements - Surge voltages
Limits according to
EN 61000-6-2
150 kHz - 80 MHz, 10 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
Limits according to
EN 61131-2
-
±2 kV, criteria B
±1 kV, criteria B
-
±2 kV, criteria B
±1 kV, criteria B
±1 kV, criteria B
±2 kV, criteria B
±1 kV, criteria B
Limits according to
EN 61131-2
±1 kV, criteria B
±2 kV, criteria B
-
-
±0.5 kV, criteria B
±1 kV, criteria B
±0.5 kV, criteria B
±0.5 kV, criteria B
±1 kV, criteria B
±1 kV, criteria B
Limits according to
EN 61131-2
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
length 3 seconds, criteria A
Limits according to
EN 55024
±1 kV, criteria B
-
-
±0.5 kV, criteria B
-
-
±0.5 kV, criteria B
-
-
Limits according to
EN 55024
±1 kV, criteria B
±2 kV, criteria B
-
±0.5 kV, criteria B
-
-
-
-
±1 kV, criteria B
-
Limits according to
EN 55024
150 kHz - 80 MHz, 3 V, 80%
amplitude modulation with 1 kHz,
criteria A
491