B&R Industries Power Panel 300 User Manual page 147

Hide thumbs Also See for Power Panel 300:
Table of Contents

Advertisement

Electrical characteristics
Bleeder resistance
Mechanical characteristics
Outer dimensions
Width
Height
Depth
Front
Frame
Design
Membrane
Dark gray border around display
Light background
Orange keys
Dark gray keys
Legend strips (gray)
Gasket
Housing
Weight
Environmental characteristics
Ambient temperature
Operation
Storage
Transport
Relative humidity
Vibration
Operation (continuous)
Operation (occasional)
Storage
Transport
Shock
Operation
Storage
Transport
Protection type
6)
Altitude
1) Maintenance controller extended.
2) At max. specified ambient temperature: typ. 50 ppm (4 seconds) - worst-case 100 ppm (8 seconds).
3) The actual value depends on the operating system or diver being used.
4) At +25°C ambient temperature. Reducing the brightness by 50% can result in an approximate 50% increase of the half-brightness
time.
5) Depending on the process or batch, there may be visible deviations in the color and surface structure.
6) Derating the maximum ambient temperature - typically 1°C per 1000 meters (from 500 meters above sea level).
Power Panel 300/400 User's Manual V 2.10
Technical data • Power Panel 300 with Automation Runtime
4PP351.0571-35 < Rev. D0
See 3.8.2 "Temperature humidity diagram" on page 148
2 - 9 Hz: 1.75 mm amplitude / 9 - 200 Hz: 0.5 g
2 - 8 Hz: 7.5 mm amplitude / 8 - 200 Hz: 2 g / 200 - 500 Hz: 4 g
2 - 8 Hz: 7.5 mm amplitude / 8 - 200 Hz: 2 g / 200 - 500 Hz: 4 g
IP20 back side (only with installed CompactFlash card)
IP65 / NEMA 250 type 4X, dust and sprayed water protection (front side)
Table 54: Technical data - 4PP351.0571-35 (Forts.)
4PP351.0571-35 ≥ Rev. D0
0 Ω
212 mm
245 mm
55.5 mm
Aluminum, naturally anodized
7)
Gray
Polyester
7)
Similar to Pantone 432CV
7)
Similar to Pantone 427CV
7)
Similar to Pantone 151CV
7)
Similar to Pantone 431CV
7)
Similar to Pantone 429CV
Flat gasket around display front
Metal
Approx. 2 kg
0 to +50°C
-20 to +60°C
-20 to +60°C
2 - 9 Hz: 3.5 mm amplitude / 9 - 200 Hz: 1 g
15 g, 11 ms
30 g, 15 ms
30 g, 15 ms
Max. 3000 m
5)
147