4.1.5 Mode / Node switches

Power Panel devices are equipped with 2 hex switches that serve as operating mode switches.
Switch positions 01 to FD are available for any purpose in an application and can be evaluated
by the application program.
Switch position
SW1 (x16)
SW2 (x1)
0
0
0 ... F
0 ... D
F
E
F
F
Power Panel 300/400 User's Manual V 2.10
Technical data • Power Panel 400 with Automation Runtime
Mode/Node switch
SW1
Table 62: Mode/Node switch
Function
Description
Boot
Automation Runtime boot mode for operating system (firmware, BIOS) upgrade (default:
Automation Runtime).
In this position, a new or missing operating system can be downloaded.
Information:
For detailed information, see chapter 4 "Software" section3 "Upgrade
information" on page 456.
Node
Automation Runtime run mode with node 01-FD (CompactFlash Automation Runtime or
terminal operation).
Freely available for CompactFlash users, e.g. setting the INA2000 node number for the
Ethernet interface.
Dyn. mode
Automation Runtime run mode with node 01-FD (CompactFlash Automation Runtime or
terminal operation).
Device addresses can be assigned through the software.
Diagnostics
Automation Runtime diagnostics mode (CompactFlash Automation Runtime or terminal
operation).
Table 63: Switch settings for the Mode / Node switch
SW2