Measuring The Operating Limit Of Set Values - ABB Relion 670 Series REL670 Commissioning Manual

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
10.4.6.1
106
Table 25:
Test points for phase-to-earth loop L3-E (Ohm/loop)
Test point
Value
1
X
[X1+XN]
R
0
2
X
0
R
RLdFw
3
X
0.85·[X1+XN]
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
4
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFFwPE·tan (ArgLd)
R
RFFwPE
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-earth loops is used together with figure 22.
Table 26:
Test points for phase-to-phase loops L1–L2
Test point
Value
1
X
X1
R
0
2
X
0
R
RLdFw
3
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5 RFFwPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFFwPP·tan (ArgLd)
R
0.5·RFFwPP
6
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
The table showing test points for phase-to-phase loops is used together with figure 23.

Measuring the operating limit of set values

Procedure:
1MRK 506 355-UEN A
Comments
XN=(X
-X
)/3
0
1
R≈0.491·(X1+XN)+RFFwPE
Comments
R=0.491·X1+0.5 RFFwPP
Line distance protection REL670 2.1 IEC
Commissioning manual