ABB Relion 670 Series REL670 Commissioning Manual page 201

Line distance protection 2.1 iec
Table of Contents

Advertisement

1MRK 506 355-UEN A
Line distance protection REL670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
The description below applies for a system with a nominal frequency
of 50 Hz but can be directly applicable to 60 Hz. SESRSYN can be set
to use different phases, phase to earth or phase to phase. Use the set
voltages instead of what is indicated below.
Figure
40
shows the general test connection principle, which can be used during
testing. This description describes the test of the version intended for one bay.
Figure
41
shows the general test connection for a 1½ breaker diameter with one-phase
voltage connected to the line side.
Test
equipment
U-Line
N
IEC05000480 V4 EN
Figure 40:
General test connection with three-phase voltage connected to the
line side
IED
U-Bus
U3PBB1
N
Input Phase
L12,L23,L31
U3PLN1
UL1
UL2
Input Phase
UL3
N
L12,L23,L31
IEC05000480-4-en.vsd
Section 10
UMeasure
Ph/N
Ph/Ph
L1,L2,L3
UMeasure
Ph/N
Ph/Ph
L1,L2,L3
195