ABB Relion 670 Series REL670 Commissioning Manual page 108

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
102
Table
24
is used in conjunction with figure 21.
Table 23:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table 24:
Test points for phase-to-earth L3-E (Ohm/Loop)
Test point
Reach
Value
1
X
(2 x X1
R
0
2
X
(2 x X1
R
2 x R1
3
X
0.8 x (2 x X1
R
0.8 x (2 x R1
Table continues on next page
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
set
set
set
set
set
set
+X0
)/3
set
set
+ X0
)/3
set
set
+ R0
)/3
set
set
+ X0
)/3
set
set
+ R0
)/3 +RFPE
set
set
1MRK 506 355-UEN A
Comments
ArgRLd = angle for the maximal load
transfer
Exact: 0.8 x RFPP/2 (ArgDir)
Exact –0.5 x R1
x
set
tan(ArgNegRes-90)
Exact –0.5 x R1
x
set
tan(ArgNegRes-90)
Only used when
OperationLdCmp
setting is 0 (Off)
Comments
set
Line distance protection REL670 2.1 IEC
Commissioning manual