ABB Relion 670 Series REL670 Commissioning Manual page 132

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
126
If the rated secondary current I
current test I
is
ts
I
I
4
I
4
A
= ×
=
ts
ovrl
rs
EQUATION14041 V1 EN
If the CT of the generator has ratio 9000/1 A, then in primary values
I
rp
I
I
I
4
=
×
= ×
t
ovrl p
,
ovrl
I
rs
EQUATION14042 V1 EN
Reference is made to the numerical values of the example, explained in the "Setting
guidelines" of the Application Manual. A test current equal to 2.5 time the base current
of the generator is chosen; this choice is related to the selected test voltage that is
applied while testing the point SE and RE.
I
2 5
.
I
2 5 8367 20918
.
=
×
=
×
t
Base
EQUATION14043 V1 EN
The parameter ReachZ1 defines the boundary between zone 1 and zone 2; it is
expressed in percent of the parameter ForwardX. If the setting of ReachZ1 = 12%,
then corresponding primary value of the reactance is
ReachZ
1
ForwardX
X
=
×
RZ 1
100
100
EQUATION14044 V1 EN
The calculation of the test voltage, that is related to ReachZ1, is based on the
impedance Z
that has imaginary part X
RZ1
Re
achZ
1
ForwardR
RRZ
1
=
×
100
100
EQUATION14045 V1 EN
The magnitude of the impedance Z
=
2
+
2
=
Z
R
X
RZ
1
RZ
1
RZ
1
EQUATION14046 V1 EN
Hence the reference voltage of the test of the boundary between zone 1 and zone 2 is
V
Z
I
0 069 20918 1435
.
=
×
=
×
t RZ
,
1
RZ
1
t
EQUATION14047 V1 EN
If the test voltage is lower than V
zone 1; if the test voltage is higher than V
Considering the resistances and reactances which are related to the settings
(ForwardR, ForwardX) and (ReverseR, ReverseX):
of the analog channel is 1 A, then the maximum
rs
9000
36000
A
=
1
A
=
12
59 33
.
×
ZBase
=
×
100
100
and real part R
RZ1
12
8 19
.
×
ZBase
=
×
100
100
is:
RZ1
2
+
2
=
W
0.009
0.068
0.069
V
=
(or in opposition), then the test is related to the
t,RZ1
, then the test is related to the zone 2.
t,RZ1
1MRK 506 355-UEN A
×
0 9522 0
.
=
.0 0 68Ω
:
RZ1
×
0 9522 0 0
.
=
. 0 0 9Ω
Line distance protection REL670 2.1 IEC
Commissioning manual
(Equation 1)
(Equation 2)
(Equation 3)
(Equation 4)
(Equation 5)
(Equation 6)