ABB Relion 670 Series REL670 Commissioning Manual page 134

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
128
Test sets usually do not have a feature to simulate a real network during a power swing
and apply the related analog quantities at the terminal of the generator. The scope of
the present test is not a simulation of a real network. Voltages and currents are supplied
in order to measure an impedance that changes in the time and traverses the plane R-
X and, in particular, the area inside the lens characteristic. The test may be performed
by applying:
Symmetric three-phase voltage at 50 Hz. The magnitude depends on the point of
the characteristic that needs to be verified. The following three main points of the
line segment SE-RE need to be checked:
the point RE (R
a point which is related to the parameter ReachZ1 (boundary between zone
1 and zone 2)
the point SE (R
The phase angle of the test voltages is equal to:
arctan (ForwardX/ForwardR) for tests in the quadrant 1 and 2 of the R-X plane
arctan (ReverseX/ReverseR) -180° for tests in the quadrant 3 and 4 of the R-X
plane
Symmetric three-phase current, where the current is the summation of two
currents that have the same magnitude, but different frequencies.
20918
I
t
I
I
=
=
=
50
tf
2
2
GUID-F02E8D18-FF87-45BE-8142-E8FA19F6966B V1 EN
The first current I
50
secondary) and phase angle 0º.
The second current I
angle 180º (at the starting time of the test) and frequency:
49.5 Hz for the test as generator in the quadrant 1 and 2 of the R-X plane
50.5 Hz for the test as generator in the quadrant 3 and 4 of the R-X plane
When the trajectory of the impedance, that is seen by the protection
function, traverses the lens characteristic then a pole slipping is
detected. The present procedure avoids tests of points of the line SE-
RE that are too close to the R-axis because in that case the voltage is
close to zero and, therefore, the impedance may approach a not
defined quantity 0/0.
The accuracy of the impedance reach is ±2% of the base impedance;
that is considered while evaluating the test results.
, X
)
FwdR
FwdX
, X
)
RvsR
RvsX
A
10459
=
has frequency 50 Hz, magnitude 10459 A (that is, 1.162 A
has magnitude 10459 A (that is, 1.162 A secondary), phase
tf
1MRK 506 355-UEN A
(Equation 16)
Line distance protection REL670 2.1 IEC
Commissioning manual