Line distance protection REL670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
Completing the test
1.
Continue to test another function or end the test by changing the Test mode setting
to Off.
2.
Restore connections and settings to their original values if they were changed for
testing purposes.
Event function EVENT
Prepare the IED for verification of settings as outlined in section
section
"Preparing for test"
During testing, the IED can be set when in test mode from PST. The functionality of
the event reporting during test mode is set in the Parameter Setting tool in PCM600.
•
Use event masks
•
Report no events
•
Report all events
In test mode, individual event blocks can be blocked from PCM600.
Fault locator LMBRFLO
Prepare the IED for verification of settings outlined in section
verify
settings".
The Fault locator function LMBRFLO depends on other functions to work properly,
that is, phase selection information from distance protection function and analog
information supplied by the trip value recorder function. Check that proper binary
start and phase selection signals are connected and voltage and current signals are
configured (parameter settings).
The result is displayed on the local HMI or via PCM600. Distances to faults for the last
100 recorded disturbances can be found on the local HMI under Main menu/
Disturbance Records/Disturbance #n(n = 1–100)/General Information
If PCM600 is used, the result is displayed on the recording list after upload, including
loop selection information.
in this chapter.
Section 10
"Requirements"
and
"Preparing the IED to