Section 10
Testing functionality by secondary injection
168
StartCurr
CT
sec
IBase
×
×
100
CTprim
IECEQUATION2432 V1 EN
Second part of the characteristic (25% of UBase ≤ Restrain voltage ≤
UHighLimit/100*UBase), valid when setting parameter VDepMode = Slope:
StartCurr
CT
sec
VDepFact
×
×
 ×
IBase
1
100
CTprim
(
)
25
UH
i i ghLimit
VT
×
×
 
UBase
100
VTprim
IECEQUATION2433 V1 EN
Third part of the characteristic (UHighLimit/100*UBase ≤ Restrain voltage):
StartCurr
CT
sec
IBase
×
×
100
CTprim
IECEQUATION2434 V1 EN
Example (rated secondary current = 1A):
CT ratio
VT ratio
StartCurr
VDepFact
UHighLimit
IBase
A test for each section of the characteristic of the function VRPVOC may be
performed; that may be achieved by applying the following voltages:
First section of the characteristic:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is lower
than 0,25*UBase; if VDepMode = Step, the minimum measured phase-to-phase
voltage is lower than UHighLimit/100*UBase:
UL1: Ampl = 10 / √3; Angle = 0°
UL2: Ampl = 10 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
Second section of the characteristic only:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is
between 0,25*UBase and UHighLimit/100*UBase:
UL1: Ampl = 50 / √3; Angle = 0°
UL2: Ampl = 50 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
Last section of the characteristic:
If VDepMode = either Slope or Step, the minimum measured phase-to-phase
voltage is higher than UHighLimit/100*UBase:
VDepFact
×
100
100
25
×
×
Re
strainVoltage
U U Base
sec
100
10 000/1A
10 kV/100 V
100%
25%
100%
10 000 A
10 kV
Line distance protection REL670 2.1 IEC
1MRK 506 355-UEN A
(Equation 89)
VT
sec
StartCurr
C C T
sec
×
+
×
×
IBase
VTprim
100
CTprim
 
(Equation 91)
Commissioning manual
VDepFact
×
100
(Equation 90)