Testing functionality by secondary injection
When the load current compensation is inactive, the dotted lines and
test point 13 are valid. Test points 5, 6, and 7 are not valid for this
measurement.
11
X1
10
40% of RLdFw
80% of RLdFw
IEC05000368 V3 EN
Figure 20:
Distance protection characteristic with test points for phase-to-phase
measurements
Table
23
is used in conjunction with figure 20.
11
X1+XN
10
40% of RLdFw
80% of RLdFw
alt. 80% of
RFPE (Load
encroachment)
IEC05000369 V3 EN
Figure 21:
Distance protection characteristic with test points for phase-to-earth
measurements
X
2
1
80%
3
50%
4
12
120°
a
5
6
R (Ohm/phase)
7
13
9
c
20°
8
0.5 x RFPP
IEC05000368-3-en
X
2
1
80%
3
50%
4
12
5
120°
a
6
7
13
9
20°
8
RFPE
IEC05000369-3-en.vsd
Section 10
R (Ohm/loop)
101