Completing The Test; Voltage-Restrained Time Overcurrent Protection Vrpvoc; Verifying The Settings - ABB Relion 670 Series REL670 Commissioning Manual

Line distance protection 2.1 iec
Table of Contents

Advertisement

1MRK 506 355-UEN A
10.5.13.2
10.5.14
10.5.14.1
Line distance protection REL670 2.1 IEC
Commissioning manual
Testing functionality by secondary injection
4.
Compare the measured time with the set value tOper.
5.
Activate the BLOCK binary input.
6.
Switch on the fault current (110% of the setting) and wait longer than the set
value tOper.
No TRIP signal should appear.
7.
Switch off the fault current.
8.
Set the measured current (fault current) in same phase to about 90% of the set
operating current IP>. Switch off the current.
9.
Switch on the fault current and wait longer than the set value tOper.
No TRIP signal should appear.
10. Switch off the fault current.

Completing the test

Continue to test another function or end the test by changing the TestMode setting to
Off. Restore connections and settings to their original values, if they were changed for
testing purposes.

Voltage-restrained time overcurrent protection VRPVOC

Prepare the IED for verification of settings outlined in section
verify
settings".

Verifying the settings

Verifying settings by secondary injection
1.
Connect the test set for three-phase current injection and three-phase voltage
injection to the appropriate IED terminals.
2.
Go to Main menu/Settings/IED Settings/Current protection/
VoltageRestOverCurr ( 51V,2(I>/U<))/VRPVOC (51V,2(I>/U<)):1/
General and make sure that the function is enabled, that is, Operation is set to
On.
3.
The test of the function may be performed by injecting restrain voltage and
increasing the injected current(s). Note the value at which the START and STOC
signals are set.
In the following equations, restrain voltage is the magnitude of
the minimum phase-to-phase voltage in secondary volts.
The set operate value in secondary amperes is calculated according to the
following equations:
First part of the characteristic (Restrain voltage ≤ 25% of UBase):
Section 10
"Preparing the IED to
167

Advertisement

Table of Contents
loading

Table of Contents