Section 4
Starting up
4.6
50
IEC13000062 V1 EN
Figure 8:
Select: Use the following IP address
6.
Use the ping command to verify connectivity with the IED.
7.
Close all open windows and start PCM600.
The PC and IED must belong to the same subnetwork for this set-up
to work.
Setting up the PC to access the IED via a network
The same method is used as for connecting to the front port.
The PC and IED must belong to the same subnetwork for this set-up
to work.

Writing an application configuration to the IED

When writing a configuration to the IED with PCM600, the IED is automatically set
in configuration mode. When the IED is set in configuration mode, all functions are
blocked. The red LED on the IED flashes, and the green LED is lit while the IED is in
the configuration mode.
When the configuration is written and completed, the IED is automatically set into
normal mode. For further instructions please refer to the users manuals for PCM600.
IEC13000062-1-en.vsd
Line distance protection REL670 2.1 IEC
1MRK 506 355-UEN A
Commissioning manual