Completing The Test; Two Step Overvoltage Protection Ov2Ptov; Verifying The Settings - ABB Relion 670 Series REL670 Commissioning Manual

Line distance protection 2.1 iec
Table of Contents

Advertisement

Section 10
Testing functionality by secondary injection
10.6.1.2
10.6.2
10.6.2.1
172
k
1
( )
=
t s
U
1
<
U
1
IECEQUATION2428 V1 EN
where:
t(s)
Operate time in seconds
k1
Settable time multiplier of the function for step 1
U
Measured voltage
U1<
Set start voltage for step 1
For example, if the measured voltage jumps from the rated value to 0.8 times the
set start voltage level and time multiplier k1 is set to 0.05 s (default value), then
the TR1 and TRIP signals operate at a time equal to 0.250 s ± tolerance.
10. The test above can be repeated to check the inverse time characteristic at
different voltage levels.
11. Repeat the above-described steps for Step 2 of the function.
Extended testing
The tests above can be repeated for 2 out of 3 and for 3 out of 3 operation mode.

Completing the test

Continue to test another function or end the test by changing the TestMode setting to
Off. Restore connections and settings to their original values, if they were changed for
testing purposes.

Two step overvoltage protection OV2PTOV

Prepare the IED for verification of settings outlined in section
verify
settings".

Verifying the settings

Verification of single-phase voltage and time delay to operate for Step
1
1.
Apply single-phase voltage below the set value U1>.
2.
Slowly increase the voltage until the ST1 signal appears.
3.
Note the operate value and compare it with the set value U1>.
The operate value in secondary volts is calculated according to
the following equations:
1MRK 506 355-UEN A
(Equation 96)
"Preparing the IED to
Line distance protection REL670 2.1 IEC
Commissioning manual